1. Trinidad and Tobago
  2. All 3M Products
  3. Electrical
  4. Splices & Accessories
  5. Cold Shrink Splices
  6. 3M™ Cold Shrink QS-III Splice Kit 5786A-MT, Longitudinally Corrugated, 25/28 kV, 1 AWG-250 kcmil (50-120 mm2), 1/case

3M™ Cold Shrink QS-III Splice Kit 5786A-MT, Longitudinally Corrugated, 25/28 kV, 1 AWG-250 kcmil (50-120 mm2), 1/case

  • 3M ID 7000140738

Splices shielded cables

Silicon rubber-splice body provides good high- or low-temperature performance and Armorcast™ jacket offers mechanical protection

Suitable for use with 10000 and 20000 Series connectors or other UL Listed inline compression connectors

View more details

Details

Highlights
  • Splices shielded cables
  • Silicon rubber-splice body provides good high- or low-temperature performance and Armorcast™ jacket offers mechanical protection
  • Suitable for use with 10000 and 20000 Series connectors or other UL Listed inline compression connectors
  • Solderless ground braid offers constant force spring connection
  • Rated for 25/28 kV applications

3M™ Cold Shrink QS-III 3/C Inline Armored or Non-Armored Cable Splices 5786A-MT, 5787A-MT and 5788A-MT are designed for splicing 3-conductor, armored and non-armored, shielded power cables. The kits are rated for use on 25/28 kV cables with conductor sizes from 1 AWG-1000 kcmil (50-500 mm²).

The kits are designed to be used with 3M™ Scotchlok™ Connectors 10000 and 20000 Series or other UL listed inline compression connectors that fit within the dimension limits listed in the connector dimensional requirements on the data sheet. The splice utilizes several technologies to accommodate the various functions of a 3/C shielded power cable: 3M™ Cold Shrink QS-III Splice Bodies, Scotch® Tapes for moisture sealing, Constant Force Springs for connecting ground braid jumpers and Armorcast for replacing the cable armor and/or jacket. The completed splice is designed for use in cable trays, weather exposed or direct burial locations. Meets the requirements of IEEE 404. Connectors are not included in the kit and must be ordered separately. Note: When making a trifurcating splice, the 3M™ Cold Shrink MT-C or MT-E Trifurcating Accessory Kit must be used along with the splice kit. Note: Cable sizes shown below are for standard insulation thickness. Final determining factor is cable insulation O.D.

Suggested applications
  • For inline splicing
  • For armored and non-armored cables
  • For 35 kV rated cables
  • For cable conductor size range of 1/0 AWG to 1000 kcmil
  • For use with solid dielectric cables; XLP, XLPE, EPR, etc
  • For indoor and outdoor applications: Cable Tray; Cable Rack; Cable Hangers; Junction Box; Aerial; and Wet or dry locations

Typical Properties